Product Details:
-
- Fully automated measurement of turns ratio, voltage ratio, phase displacement and excitation current.
- Highest measurement accuracy in the industry of up to 0.03% makes the 2796 the perfect tool for preventive maintenance measurement
- Automatic winding connection identification AWCI (patent pending) and automatic vector group detection supports the quick and easy operation
- Build-in printer for quick test report generation and total prevention of data loss
- Lightweight, compact and rugged design for use in harsh environments. Closed case is IP65 waterproof, open case is splash proof
- Remote control software to operate the unit from a laptop PC and for easy gathering exchanging and analyzing of measurement data.
- Ratios of up to 50’000 can be measured
- Better transformer excitation due to higher test voltage of 250V
- Quick setup with intuitive guide-through user interface. Test setups and results can be stored and recalled, printed out with the built-in printer or used for later analysis
- Safety connection control feature proofs test setup before applying regular test voltage to guarantee safety of the personnel and instrument.
- Remote tap changer switch enables convenient testing of multi-tap transformers.
- Measurement of phase displacement of transformers with irregular vector groups like: phase shifting, rectifier, arc-furnace and traction transformers.
Applications:
- Power- and distribution transformers
- Special transformers like phase shifting-, rectifier-, arc-furnace- and traction- transformers
- Instrument transformers
Communication Capabilities:
- Remote control software to operate the unit from a laptop PC and for easy gathering exchanging and analyzing of measurement data
- (Free external application software allows data exchange and advanced analysis of results on a computer (USB connection) including automatic report generation.)
Accessories:
- 2796/APS: Arbitrary Phase Shift Software to measure special type of transformers with phase deviation outside 30° steps (e.g. -7.5° or 22.5°)
- 279X/TAP: External test switch for tap changer testing, 20m
- 279X/10: Extension cables (2 pieces), 3-phase, 10m each
- 279X/SINGLE: Single phase measuring cable (2 pieces), 5m each
- 279x/WE2: Warranty Extension to 2 years for 2795/2796
- 279x/WE3: Warranty Extension to 3 years for 2795/2796